nVent explains how hat need to be managed with equipping the right CDUs is vital in powering the next generation liquid cooling that will be the backbone of the data centres of the future.
Liquid cooling does not need to be all or nothing. Data centres can consider cooling a single rack or a small set of racks where AI and machine learning applications are housed without deploying full scale data halls that are liquid cooled and support rack after rack of equipment running high performance computing solutions.
However, when implementing these spot solutions, understanding future business plans is critical. Using dedicated cooling solutions to solve a unique problem is important, but due to cost, energy efficiency and other factors, a solution for one problem may not be the solution for another. As with all data centre projects, different challenges require different solutions, and a one-size-fits-all approach rarely succeeds.
With the growth in demand for high performance computing (HPC) driven by the expansion of AI, data centre managers need to have a plan in place to scale their cooling solutions. This may mean planning next generation data centres to be fully liquid cooled, or exploring hybrid liquid to air solutions, such as rear door cooling or direct-to-chip CDUs, that bring liquid cooling to the rack and chip level while operating within air-cooled infrastructure.
The biggest advantage that planning for the future and understanding IT workloads will bring is the realisation that almost all potential cooling solutions can be built out in combinations, allowing data centre managers to match their power and cooling capabilities with shifting demands. The key to sustainable growth is a variety of flexible options for supporting the next-generation equipment. Liquid cooling technologies help drive that flexibility.
Unpacking CDU motors: It’s not just about redundancy
Liquid cooling is here. Next-generation chips and other AI infrastructure need more efficient cooling methods to keep them from overheating. Today, many data centres implement solutions that remove extra heat by increasing air volume or reducing air inlet temperatures, which can be inefficient and costly to run. When air cooling systems must work harder to maintain optimal temperatures, facilities can also face equipment breakdowns, unexpected shutdowns and increased energy costs.
For many data centres, using liquid cooling technologies can offer better performance while reducing energy use and helping data centres operate more efficiently. For the most advanced applications, liquid cooling is the only possible option. By using liquid cooling technologies in the right way, data centre managers can greatly improve Power Usage Effectiveness (PUE), even in applications where they are using next-generation IT.
A critical part of any liquid cooling system is the coolant distribution unit, or CDU. The CDU acts as the ‘heart’ of the liquid cooling system, pumping cooled fluid through racks at an appropriate rate for the cooling needs of the system. CDUs need to dynamically respond to the cooling needs of IT by changing the rate at which fluid flows through the system. However, there are a few methods of controlling CDU pumps. Each method has benefits and drawbacks.
Powering the data centre’s heart
There are two main types of drives used in CDU pump motors: variable speed drives (VSDs) and variable frequency drives (VFDs). Both adjust the speed that motors run to respond to the cooling demands of IT systems, circulating liquid through the system at different rates. However, there is a key difference between them.
VSDs manage motor velocity using amperage and voltage, supplying less net input voltage when the motor doesn’t need to run as fast. This is achieved by rapidly cycling the pump on and off to achieve the desired pump speed. VFDs present an interesting alternative to this method, using voltage and frequency instead of amperage to control the motor’s operation. Using voltage and frequency together allows greater control over a motor’s speed and torque, helping motors last longer while minimising energy waste.
VFDs also work better and retain efficiency better than VSDs when motors are running at lower capacity. Additionally, VSDs can introduce harmonic distortion into systems that affect power quality for cooling systems. They can also overheat when operating at reduced speeds, which can necessitate extensive maintenance and potential down time.
For these reasons, data centres that require constant uptime should consider CDUs with VFD motors. Data centre managers also need to ensure their CDU motors are concurrently maintainable, meaning they can be replaced without the CDU going offline and interrupting the liquid flow to the IT equipment. While redundancy is always important for CDU motors, the reliability of VFD motors means that fewer redundancies might be necessary for VFDs than VSDs.
More is not always more
While data centres require 24/7 uptime, adding multiple redundant motors can add failure points to a cooling system and running many pumps simultaneously hurts the partial PUE of the system. An alternative approach is to have one pump that can do all the cooling and one backup to pick up slack in case of maintenance issues.
Both VFDs and VSDs allow for varying flow rates of a pump – but with VSD control, pump voltage is cycled rapidly to get the desired speed. This can create large current spikes affecting system power quality and, in some cases, can create large fluctuations in liquid pressure that need to be managed with additional diaphragm or bladder expansion tanks. To compensate for this, CDUs with VSD controlled motors often have additional pumps added not just for redundancy but to ensure that cooling demands are met over a wide liquid flow operating range. Operating more pumps than necessary, in many cases, leads to inefficiency in power consumption and increases the overall failure domain of the solution.
In addition to the motor type, data centre managers should look at the coupling methods within CDU pumps. Magnetically coupled pumps with VFD motors are extremely unlikely to leak and are very reliable, minimising the need for multiple redundancies and lowering energy use. When pumps are magnetically coupled, as opposed to mechanically sealed, components can be physically separated, minimising mechanical vibrations and preventing wear and tear. Additionally, the separation between the drive shaft and pump components allows for a completely sealed enclosure on the pump’s liquid end. This removes another potential failure point by eliminating the need for a mechanical seal between the motor drive shaft and liquid-carrying components.
Equipping a data centre with the right CDUs to power next generation liquid cooling is critical to the functioning of future data centres. Examining motor control and coupling methods for CDU pumps is just one piece in a complicated equation, but it should not be ignored, because when the liquid stops flowing, the IT equipment shuts down.